Touch Panel Display
VT3 series
6-inch VGA TFT Colour Touch Panel VT3-V6H
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
Model | VT3-V6H | |||
General specifications | Current consumption | 380mA or less | ||
Structure | IP65f equivalent dust proof, waterjet proof | |||
Overvoltage category | I | |||
Pollution degree | 3 | |||
Power voltage | 24 VDC ±10% | |||
Noise resistance | 1500 Vp-p pulse width 1 µs 50 ns (common mode, based on noise simulator) | |||
Withstand voltage | 1500 VAC 1 minute (between power terminal and housing) | |||
Insulation resistance | 50 MΩ or more tested by 500 VDC megohmmeter (between power terminal and housing) | |||
Vibration resistance | Intermittent vibration | Frequency: 5 to 9 Hz | Half amplitude:3.5 mm*1 | |
Frequency: 9 to 150 Hz | Acceleration: 9.8 m/s2*1 | |||
Continuous vibration | Frequency: 5 to 9 Hz | Half amplitude:1.75 mm*1 | ||
Frequency: 9 to 150 Hz | Acceleration: 4.9 m/s2 *1 | |||
Ground | Class D grounding (Class 3 grouding). | |||
Operating environment | Minimal amount of dust and corrosive gas present | |||
Ambient operating temperature | 0 to +50°C *2*3 | |||
Ambient operating humidity | 35 to 85%RH (No condensation)*4*3 | |||
Ambient storage temperature | -10 to +60°C (No freezing) | |||
Ambient storage humidity | 35 to 85%RH (No condensation)*4*3 | |||
Drop | According to JIS B 3502 IEC61131-2 (1.3m) | |||
Weight | Approx 1100g*5 | |||
Performance specifications | Displaypanel | Display elements | TFT colour LCD | |
Display colour | 32768 colours | |||
Number of points displayed | W 640 × H 480 points | |||
Active display area | W 132.5 × H 99.4 mm | |||
Service life (normal temperature andhumidity) | Approx 50000 h | |||
Backlightlamp | System | White LED (Not replaceable) | ||
Life-span | Approx 50000 h | |||
Touchswitch | Number of switches | 80×60/screen | ||
System | Analogue resistive membrane type | |||
Operating force | 0.98N or less | |||
Life-span | 1,000,000 times or more | |||
Screen data internal memory | Memory capacity | 12 MB (memory extension enabled) | ||
Number of pages that can be registered | Up to 1024 pages | |||
Number of screens that can be registered | Up to 1024 screens | |||
Page No.: 0 to 8999, Global window No.: G000 to G999, Report screen P.00 to P.15 | ||||
Data backup | Screen data | Flash ROM can be erased 100000 times. | ||
Recording data | SRAM backup:lithium battery | |||
Character font | Outline font, Bitmap font, Stroke font Windows font, IMAGE font, Small font | |||
Calendar timer | Accuracy: ±40s/month (25°C), Backup:lithium battery (5 years above of service life at 25°C) | |||
Communication function | PLC host link | KEYENCE, Mitsubishi Electric, OMRON, Sharp, Fuji Electric FA Components & Systems, Yaskawa Electric, Hitachi, Panasonic Electric Works, JTEKT (Toyota), | ||
Thermostat | Yokogawa Electric, Azbil (Yamatake), OMRON, RKC Instrument, Shinko Technos, CHINO | |||
Inverter | Mitsubishi Electric, Fuji Electric FA Components & Systems, Yaskawa Electric, OMRON | |||
Servo amplifier | Mitsubishi Electric | |||
Stepping motor | Orienltal Motor | |||
Robot controller | IAI | |||
Eco-power meter | Panasonic Electric Works | |||
General-purpose communication | Based on specific commands | |||
I/O specifications | Function switch (FSW1/FSW2/FSW5/FSW6) | Number of outputs | 4 (FSW1, FSW2, FSW5, FSW6) | |
Common terminal | 4 terminals/common (FSWC) | |||
Output | MOSFET (N-ch; with overcurrent protection function) | |||
Rated load | 30 VDC 0.1 A | |||
Leakage current (at OFF) | 100 µA or less | |||
Residual voltage (at ON) | 1.0V or less | |||
Durability | 300,000 times or more | |||
Enabling switch (EN1A/EN1B/EN2A/EN2B) | Rated voltage | 30 VCD | ||
Rated current | ― | |||
Contact method | ||||
Durability | Mechanical | |||
Electrical | ||||
Function | ||||
RS-232C/422 communication (CN2A/CN2B) | Applied standard | Conforms to EIA RS-232C and RS-422 | ||
Synchronisation between the transmitter and receiver | Start-stop, full duplex | |||
Communication distance | 15m (RS-232C)/500m (RS-422) | |||
Data length | 7 or 8 bits | |||
Parity | Even, odd, none | |||
Communication speed | 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps | |||
Ethernet communication (CN3) | Compliance | IEEE802.3 | ||
Transmission speed | 10 Mbps (10BASE-T),100 Mbps (100BASE-TX) | |||
Transmission medium | STP or category 3 or higher UTP (10BASE-T), STP or category 5 or higher UTP (100BASE-TX)*6 | |||
Maximum cable length | 100 m | |||
Maximum number of connectable hubs | 4 (10BASE-T),2 (100BASE-TX) | |||
Maximum number of connections | PC application:*7 3, | |||
MegaLink/multi-link (A/B/G) | When connected through MegaLink | Applied standard | RS-485 | |
Synchronisation between the transmitter and receiver | Start-stop, half duplex | |||
Communication speed | 19,200 bps, 115,200 bps, 0.5 Mbps, 1 Mbps, 2 Mbps | |||
Cable connection | Multi-drop (branching is not possible) | |||
Maximum number of connectable units | 15 | |||
Baud rate 19200 | Maximum extension distance: 1,000 m | |||
Baud rate 115200 | ||||
Baud rate 0.5 M | Maximum extension distance: 500 m | |||
Baud rate 1 M | Maximum extension distance: 200 m | |||
Baud rate 2 M | Maximum extension distance: 100 m | |||
When connected through VT multi-link | Applied standard | RS-485 | ||
Synchronisation between the transmitter and receiver | Start-stop, half duplex | |||
Communication distance | Maximum extension distance: 500 m or less | |||
Communication speed | 19200, 115200, 0.5M, 1M bit/s | |||
Baud rate 115200 or less | Maximum extension distance: 500 m | |||
Baud rate 0.5 M | Maximum extension distance: 100 m | |||
Baud rate 1 M | Maximum extension distance: 50 m | |||
When connected through multi-link | Applied standard | RS-485 | ||
Synchronisation between the transmitter and receiver | Start-stop, half duplex | |||
Communication distance | Maximum extension distance: 500 m or less | |||
Communication speed | 19200, 38400, 57600, 115200 bit/s | |||
*1 Conforms to JIS B 3502, IEC61131-2 |